APPLICATIONS Heating, ventilation and air conditioning (HVAC); hood and gas cabinet monitoring; cleanroom and cleanbench face velocity monitoring. PHYSICAL DATA
SUGGESTED SPECIFICATIONS Air velocity transmitter shall be an insertion type mass flow meter with accuracy of ±1% FS, +0.5% of reading and a 0.2 second response time. Transmitter shall provide a 4-20 mA output signal linearly proportional to gas mass velocity. Insertion probe shall be constructed of 304 SS with a glass coated sensor assembly. Electronics shall be housed in a NEMA 2 enclosure. Air velocity transmitter shall be Dwyer Model No, PF _____. |